Dry Cooler / Fluid Cooler Calculator

Guide for dry cooler and fluid cooler sizing: approach temperature, glycol concentration, fan power, and ambient conditions.

1. Overview

A dry cooler (also called fluid cooler or dry fluid cooler) rejects heat from a process fluid to ambient air without evaporative cooling. The fluid circulates through finned-tube coils while fans force ambient air across the finned surface. Unlike cooling towers, dry coolers have no water consumption and minimal maintenance.

The key design parameter is the approach temperature — the difference between the fluid outlet temperature and the ambient air temperature. Lower approach temperatures require larger coil surface area.

2. Input Parameters

Air Side

ParameterUnitDescription
Dry Bulb Temperature°CAmbient air temperature (design condition)
Face Velocitym/sAir velocity across coil face (typically 2–4 m/s)
AltitudemInstallation altitude

Fluid Side

ParameterUnitDescription
Fluid Type—Pure Water, Ethylene Glycol, or Propylene Glycol
Inlet Temperature°CHot fluid entering the cooler
Outlet Temperature°CTarget fluid outlet temperature
Flow Ratekg/hMass or volumetric flow rate

3. Approach Temperature

The approach temperature (T_fluid_out − T_air_in) is the most critical design parameter:

ApproachCoil SizeApplication
> 10 KCompactProcess cooling with high fluid temperatures
5–10 KStandardGeneral HVAC and industrial cooling
3–5 KLargeData center cooling, free cooling
< 3 KVery largeEconomically challenging, consider hybrid coolers

The fluid outlet temperature can never be lower than the ambient air temperature in a dry cooler. If lower temperatures are needed, consider an evaporative (wet) cooling tower or a hybrid cooler.

4. Glycol Effects

Glycol is commonly added for freeze protection in outdoor installations. However, it significantly impacts performance:

  • 30% ethylene glycol: ~15% capacity reduction, ~40% higher pressure drop
  • 50% ethylene glycol: ~25% capacity reduction, ~100% higher pressure drop
  • Propylene glycol has even higher viscosity than ethylene glycol at the same concentration

Tip: Use the minimum glycol concentration needed for the expected minimum temperature plus a 5°C safety margin. Over-concentrating glycol wastes pump energy and reduces heat transfer.

5. Applications

  • Data Centers: Free cooling when ambient temperature is low enough to reject server heat without mechanical refrigeration
  • Process Cooling: Cooling process fluids (hydraulic oil, cutting fluid, glycol loops)
  • Chiller Condenser Water: Rejecting heat from water-cooled chillers without a cooling tower
  • Heat Pump Rejection: Heat rejection loop for water-source heat pump systems