Chilled water and glycol cooling coils
Chilled water coil selection and rating software
Select cooling coils for air handling units and fan coils. ExCoil marches row by row in counter-cross flow, separates dry and wet surface and reports capacity, sensible heat ratio, leaving air, water temperature rise and pressure drop.
Calculator included in the free plan · The calculator interface is available in English and Portuguese.

Real application screenshot
What it calculates
- Row-by-row counter-cross-flow model with water entering at the air-leaving row
- Dry and wet surface by enthalpy potential, latent load and condensate
- Water or ethylene glycol mixtures
- Physical tube count, circuits and passes with water velocity checks
- Header and connection sizing with commercial pipe diameters
- Maldistribution and fouling as area derating, not as a change of flow
Results and deliverables
- Total and sensible capacity, SHR, leaving dry-bulb and wet-bulb
- Water outlet temperature, velocity and pressure drop
- Air pressure drop and face velocity
- PDF report, 2D drawing and DXF (Professional)
- 3D model with headers, STL and STEP, circuitry and header tabs (Enterprise)
How the chilled water model works
The water-side coefficient uses VDI/Gnielinski with a continuous transition, the air side uses Wang–Chi–Chang with the actual fin thickness, and the energy balance between air and water closes to numerical precision. Header diameters follow the actual flow, so a 40 TR coil does not receive a 19 mm connection.
- Row-by-row counter-cross-flow marching
- Wang–Chi–Chang (2000) air side, Schmidt fin efficiency
- VDI / Gnielinski water side
- Water pressure drop without double counting passes
- ASHRAE psychrometric equations
Know the limits
- Glycol is modelled as ethylene glycol by mass fraction.
- Drain pan, casing and fan are not part of the calculation.
- Use the results as engineering estimates; validate before catalogue publication.
Frequently asked questions
Can I select a chilled water coil for an air handling unit?
Yes. Enter airflow, entering air and water conditions, and ExCoil returns capacity, SHR, leaving air and water pressure drop for the selected geometry.
Are glycol mixtures supported?
Yes, ethylene glycol by mass percentage in the chilled and hot water coil modules; the dry cooler module also supports propylene glycol.
How are the headers sized?
From the real water flow and velocity targets, using commercial pipe diameters. The same headers appear in the 2D drawing, the 3D model and the report.
Other modules
- DX evaporatorCapacity, SHR, superheat and refrigerant ΔP with rating, sizing and TXV modes.
- Condenser coilDesuperheating, condensing and subcooling zones with real refrigerant enthalpies.
- Hot water coilHeating and reheat coils with water velocity and pressure drop checks.
- Steam coilIn-tube condensation, steam consumption and condensate sizing.
- Dry coolerWater and glycol fluid coolers with balanced sizing and V-shape layouts.
- Shell & tubeBell-Delaware, TEMA types, drawings, STEP, BOM and weights from one model.