ExCoil
HVAC

Chilled Water Coil Selection: AHU Design Guide

Complete guide to selecting and sizing chilled water coils for air handling units, including water flow rates, glycol effects, and dehumidification analysis.

January 5, 202611 min read

Chilled water coils are essential components in central air conditioning systems. This guide covers the selection and sizing process for optimal performance.

Chilled Water System Basics

Typical Operating Conditions

  • Supply water temperature: 6-7°C (42-45°F)
  • Return water temperature: 12-14°C (54-57°F)
  • Temperature difference (ΔT): 5-7 K

Water Flow Calculation

ṁ = Q / (c_p × ΔT)

Where:

  • ṁ = mass flow rate (kg/s)
  • Q = cooling capacity (kW)
  • c_p = specific heat (4.18 kJ/kg·K for water)
  • ΔT = temperature difference (K)

Coil Selection Process

Step 1: Define Air-Side Requirements

  • Air flow rate (m³/h or CFM)
  • Entering air conditions (DB/WB or DB/RH)
  • Leaving air conditions (target)

Step 2: Calculate Cooling Loads

  • Sensible cooling: Temperature reduction
  • Latent cooling: Moisture removal
  • Total cooling: Sum of both

Step 3: Determine Water-Side Parameters

  • Available supply temperature
  • Allowable pressure drop
  • Flow rate constraints

Step 4: Select Coil Geometry

  • Face area (based on velocity)
  • Number of rows (based on capacity)
  • Fin spacing (based on application)

Sensible Heat Ratio (SHR)

SHR = Q_sensible / Q_total

Typical SHR Values

  • Office spaces: 0.75-0.85
  • Retail: 0.70-0.80
  • Hospitals: 0.65-0.75
  • Data centers: 0.95-1.0

Coil Design Impact

  • Low SHR = more rows needed
  • High SHR = fewer rows, higher velocity OK

Dehumidification Considerations

Apparatus Dew Point (ADP)

The effective surface temperature of the coil:

ADP = T_wb,in - BF × (T_wb,in - T_water,avg)

Where BF is the bypass factor.

Bypass Factor

Fraction of air that doesn't contact the coil surface:

  • 4-row coil: BF ≈ 0.15-0.25
  • 6-row coil: BF ≈ 0.05-0.15
  • 8-row coil: BF ≈ 0.02-0.08

Ensuring Dehumidification

  • Coil surface must be below dew point
  • Lower water temperature = better dehumidification
  • More rows = lower bypass factor

Glycol Effects

Why Use Glycol?

  • Freeze protection
  • Lower operating temperatures
  • Required for some applications

Performance Impact

Glycol % Freeze Point Capacity Reduction
0% 0°C 0%
25% -12°C 5-8%
35% -20°C 10-15%
50% -34°C 20-25%

Compensation Strategies

  • Increase coil size
  • Lower water temperature
  • Increase flow rate

Water-Side Design

Velocity Limits

  • Minimum: 0.5 m/s (avoid stratification)
  • Maximum: 2.5 m/s (erosion, noise)
  • Optimal: 1.0-2.0 m/s

Pressure Drop

  • Typical: 20-50 kPa
  • Higher ΔP = more pump energy
  • Consider system curve

Circuiting Options

  • Series: Higher velocity, more ΔP
  • Parallel: Lower velocity, better distribution
  • Counter-cross flow: Best thermal performance

Control Strategies

Two-Way Valve

  • Variable flow
  • Better for variable load
  • Requires variable speed pumping

Three-Way Valve

  • Constant flow
  • Simpler control
  • Higher pump energy

Face and Bypass

  • Constant water flow
  • Air bypasses coil
  • Good humidity control

Common Selection Mistakes

  1. Undersizing for dehumidification

    • Check ADP vs. required dew point
    • Add rows if needed
  2. Ignoring glycol effects

    • Always account for capacity reduction
    • Verify freeze protection adequate
  3. Excessive water velocity

    • Causes erosion and noise
    • Increases pump energy
  4. Insufficient air-side clearance

    • Affects air distribution
    • Reduces effective capacity

Conclusion

Proper chilled water coil selection requires balancing air-side and water-side parameters while considering dehumidification requirements and system constraints. Using professional selection software ensures accurate sizing and optimal performance.

Tags

chilled waterAHUglycoldehumidification

Share this article